Internal Accessories
Auxiliary Switches
5.)
Secure the trip unit in place with the retaining screw
located at the top of the trip unit. Torque to 6-8 in. lbs. If
trip unit top is not secured properly, the interlock will
prohibit closing of the breaker.
6.)
Replace the front cover of the breaker, being careful not
to pinch wire leads routed to secondary disconnects or
terminal blocks. Secure with eight (8) Phillips head screws.
Installation of the auxiliary switch is complete.