64
External Accessories
This system will provide Class 1 ground fault protection as
described in UL STANDARD 1053. GROUND-FAULT SENS-
ING AND RELAYING EQUIPMENT.
System Components
UL Listed Circuit Breaker Components and Accessory Com-
ponents
1. Circuit Breaker
Table 2
2. Trip Unit-
Table 1
3. Rating Plug-
Table 3
4. GF Monitor Module
SBGFM
5. Display Module Relay
Table 4
or Remote Indicator Panel-
SBRIP120
6. Shunt Trip Device-
Table 5
Ground Fault Sensing and Relaying
Table 1- Trip Unit
SB04TLI
SB12TLI
SB20TLI
SB32TLI
SB04TLS
SB12TLS
SB20TLS
SB32TLS
SB04TLSI
SB12TLSI
SB20TLSI
SB32TLSI
SB04TLIG
SB12TLIG
SB20TLIG
SB32TLIG
SB04TLSG
SB12TLSG
SB20TLSG
SB32TLSG
SB04TLSIG
SB12TLSIG
SB20TLSIG
SB32TLSIG
SB08TLI
SB16TLI
SB25TLI
SB40TLI
SB08TLS
SB16TLS
SB25TLS
SB40TLS
SB08TLSI
SB16TLSI
SB25TLSI
SB40TLSI
SB08TLIG
SB16TLIG
SB25TLIG
SB40TLIG
SB08TLSG
SB16TLSG
SB25TLSG
SB40TLSG
SB08TLSIG
SB16TLSIG
SB25TLSIG
SB40TLSIG
Table 2-Circuit Breaker
SBA0804
SBA0808
SBA1212
SBA2016
SBA2020
SBS0804
SBS0808
SBS1212
SBS2016
SBS2020
SBS4025
SBS4032
SBS4040
SBH0804
SBH0808
SBH1212
SBH2016
SBH2020
Table 3-Rating Plug
04SB200
04SB225
04SB250
04SB300
04SB350
04SB400
04SB400
04SB450
04SB500
04SB600
04SB700
04SB800
12SB600
12SB700
12SB800
12SB1000
12SB1200
16SB800
16SB1000
16SB1200
16SB1600
20SB1000
20SB1200
20SB1600
20SB2000
25SB1600
25SB2000
25SB2500
32SB1600
32SB2000
32SB2500
32SB3000
40SB2000
40SB2500
40SB3000
40SB3200
Table 4-Display
Module
SBDMR24
SBDMR48
SBDMR120
SBDMR125
Table 5-Shunt Trip
SBST12
SBST24
SBST48
SBST125
SBST120
SBST240
SBST480
System Description:
This Ground Fault Relaying system is based on the Type SB
insulated case circuit breaker. The breaker must be equipped
with an electronic Trip Unit and Rating Plug. The trip unit can
be the type with or without the built-in ground fault tripping
function. The breaker must also have a GF Monitor Module, a
Shunt Trip Device, and either a Display Module Relay or
Remote Indicator Panel. For a system completely enclosed
within the breaker case, the internally mounted Display Mod-
ule Relay is used . If remote cause of trip information is
required, the Remote Indicator Panel may be used in place of
the Display Module Relay.
Ground Fault Relaying System
System Operation:
The user must first set the desired ground fault pickup and
delay settings on the Ground Fault Monitor Module (Page 63).
These settings are independent from the trip unit built-in
ground fault settings (if available). When a ground fault above
the selected pickup occurs, the breaker will delay based on
the module settings and when the proper time has elapsed.
Issue a signal to the internal Display Module Relay or External
Remote Indicator Panel. The output contacts of the relay can
then be used to trigger the Shunt Trip Device, thus tripping the
circuit breaker.
Testing:
General Instructions
1.
The interconnected system shall be evaluated when
initially installed by qualified personnel. It is also recom-
mended that this be done periodically thereafter.
2.
The proper location of the sensors around the bus of the
circuit to be protected shall be determined. This can be
done visually with knowledge of which bus is involved.
3.
The grounding points of the system shall be verified to
determine that ground paths do not exist that would
bypass the sensors.
4.
The polarity of the sensor connections must agree with
the installation instructions to avoid improper operations.
5.
A simulated test is to be done using a low voltage, high
current source. This test is not intended to verify that it is
properly functioning.
6.
The results of this testing should be recorded on the form
provided at the end of this document or other appropriate
forms and should be available to the inspection authority.
7 . These breakers may be set for different modes of opera-
tion. Residual or Ground Return, as described in the
information on applications, refer to the NEMA standards
publication No. PB 2.2 Application Guide for Ground
Fault Protective Devices for Equipment.
Summary of Contents for SBA 1200
Page 68: ...66 External Accessories Ground Fault Sensing and Relaying Courtesy of NationalSwitchgear com ...
Page 94: ...92 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 95: ...93 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 100: ...98 Courtesy of NationalSwitchgear com ...
Page 101: ...Electrical Diagrams 99 Courtesy of NationalSwitchgear com ...
Page 102: ...100 Electrical Diagrams Courtesy of NationalSwitchgear com ...