Connection to an Entro Lite DC800 Door Controller
Configuration
Following jumper selections must be done:
•
Reader type (J4) must be put on the Wiegand
•
Voltage jumper (J1) to VIN
•
Function jumper (J3) to Entro Lite
•
(Note - if the DC800 is used in Entro - set J3 to Entro)
Operation
When the Reader is powered the LED is flashing for 5 seconds. After these 5
seconds the LED flashes by the sequence red, yellow and green before the LED is
switched off and the Reader is ready for use.
When a Smart Card is provided within the reading sector of the SC7 and the card is
accepted, the yellow LED is lit for approximately 0.5 seconds at same time as a message
is sent out. The yellow LED is only lit when a message is sent out from the Reader. After
this the Reader goes back to wait state, code from the same card is not sent again before
a time of 3 seconds has been elapsed provided the card has been out of the reading
sector.
Technical Specifications
Power Supply:
24V (+10 / +30 V)
Current consumption:
100mA max
Interfaces:
Wiegand
Clock and Data
Housing:
Plastic
Dimensions:
SC7: 110 x 43 x 24
(H x W x D)mm:
SC7P:138 x 43 x 24
Temperature:
-
40 to 55°C
Storage temperature:
-40 to 55°C
IP Rating:
SC7:IP67
SC7P:IP47
Connection:
3m cable
Led:
Tricolor
Buzzer:
Yes
Carrier frequency:
13.56 MHz
Summary of Contents for SC7