Network topologies / media redundancy
2.4 MRP
SCALANCE X-200
26
Operating Instructions, 12/2011, A5E00349864-19
Topology
The following schematic shows a possible topology for devices in a ring with MRP.
10
9
8
7
6
5
4
3
2
1
5HGXQGDQF\GRPDLQ
+0,VWDWLRQ
(QJLQHHULQJVWDWLRQ
(76
(70
(7SUR
6ZLWK&3$GYDQFHG
6&$/$1&(;VZLWFK
3&ZLWK&3
6ZLWK&3$GYDQFHG
Figure 2-9
Example of a ring topology with the MRP media redundancy protocol
The following rules apply to a ring topology with media redundancy using MRP:
●
All the devices connected within the ring topology are members of the same redundancy
domain.
●
One device in the ring is acting as redundancy manager.
●
All other devices in the ring are redundancy clients.
Non MRP-compliant devices can be connected to the ring via a SCALANCE X switch or via
a PC with a CP 1616.
Note
SCALANCE X-300 - modular devices (M)
Remember that in the modular switches the ring ports are located on MM900 media
modules.
Summary of Contents for SCALANCE X-200
Page 12: ...Table of contents SCALANCE X 200 12 Operating Instructions 12 2011 A5E00349864 19 ...
Page 284: ...Technical specifications SCALANCE X 200 284 Operating Instructions 12 2011 A5E00349864 19 ...
Page 288: ...References SCALANCE X 200 288 Operating Instructions 12 2011 A5E00349864 19 ...
Page 294: ...Dimension drawings SCALANCE X 200 294 Operating Instructions 12 2011 A5E00349864 19 ...