3
Operation by Front Panel
2. Load b6 into the phase Curve Type register, and b5 into the
ground Curve Type register.
3 . Enter 7 0 into the phase Tap Cal register, and 20 into the
ground Tap Cal register.
4. Enter 4.7 into the phase instantaneous #1 overcurrent
register, and 4 . 27 into the ground Instantaneous #1 Over
current register.
5. Enter 07 into the phase TIME DIAL register, and 05 into the
ground TIME DIAL register.
Page
16
www
. ElectricalPartManuals
. com