Outputs
Resistive:
Inductive:
Shock
Vibration
Isolation
Surge Withstand Capability
Radio Frequency Interference
(RFI)
Temperature (Operating)
Temperature (Storage)
Weight
Case Size
Certification
Table C.1
Specifications (continued)
Output contacts are rated as follows:
1 20/240 Vac - Make 30 A for 0.2 seconds, carry 7 A continuously, break 7 A.
250 Vdc - Make and carry 30 A for 0.2 seconds, carry 7 A continuously, break 0.3 A.
500 Vdc - Make and carry 1 5A for 0.2 seconds, carry 7 A continuously, break 0.1 A.
1 20/240 Vac, 1 25/250 Vdc - Break 0.3 A (UR
=
0.04).
In standard tests the relay has withstood 1 5 g in each of three mutually perpendicular
axes, without structural damage or degradation of performance.
In standard tests the relay has withstood 2 g in each of three mutually perpendicular
axes, swept over the range of 1 0 to 500 Hz for a total of six sweeps, 1 5 minutes each
sweep, without structural damage or degradation of performance.
1 500 Vac at 60 Hz for one minute, in accordance with IEC 255-5 and ANSI/IEEE
C37.90- 1 989 (Dielectric Test).
Qualified to ANSI/IEEE C37. 90. 1 - 1 989 Standard Surge Withstand Capability Test and
FastTransient Test, and IEC 255-5 Impulse Test and Dielectric Test.
Maintains proper operation when tested in accordance with ANSI/IEEE
C37 .90.2-1 987.
-40° to 70°C (-40° to 1 58°F).
-65° to 1 00°C (-85°tO 21 2°F}
1 4.8 pounds net
S1 . (Dimensions are given in Figure 4.)
Ul pending.