| Types SDV-R and SDV-R-AR distribution circuit breakers
Current transformers (CTs)
Figure 6: Type SDV-R distribution circuit
breaker with interphase barriers and bushing
current transformers installed in primary
compartment on page 16 illustrates the
location of bushing (toroidal) CTs installed in
the primary compartment of a type SDV-R
distribution circuit breaker. The roof bushings
pass through the CTs. Up to two CTs may be
mounted around each roof bushing. The
bushing CT connections are wired to separate
terminal blocks located in the relay and
control compartment.
Hazardous voltages.
Will cause death, serious injury or property damage.
Do not operate current transformers with the secondary open circuited.
Current transformers must be either connected to a load or short
circuited. Current transformer secondary circuits also must be
grounded.
Phase barriers
Phase barriers are provided on all type SDV-R
distribution circuit breakers as shown in
Figure 6: Type SDV-R- distribution circuit
breaker with interphase barriers and bushing
current transformers installed in primary
compartment. These plates of insulating
material provide suitable electrical insulation
between the primary circuit elements.