Technical specifications
10.1 Technical specifications – accessories
3KF switch disconnectors with fuses
Manual, 09/2019, L1V30580914002A-01
111
Regulations
IEC 60947-1, IEC 60947-3, VCE 0660 Part 107
Size
1
2
3
4
5
Main conductor connection
Conductor cross-section, max.
Busbar systems, max. dimensions
(number x width x thickness)
Tightening torque
mm²
mm
Nm
25
1x9x2
5 ... 6.5
95
1x20x3
15 ... 22
240
1x25x
3
30 ...
44
2x150
1x30x
10
30 ...
44
2x300
1x50x10
50 ... 75
1)
Max. permissible operating temperature at connections 125 °C
2)
Values valid even at +10% line voltage tolerance in case of AC
3)
Values are provided as a guide only and may vary depending on the make of motor
4)
Valid for combination of 3KF and fuse type 3NA/3ND, characteristic gG/aM
10.1
Technical specifications – accessories
Additional poles
The technical specifications of the additional poles – 4th contact element, N terminal, and
N/PE terminal – correspond to those of the 3KF main switch.
See chapter 3 and 4-pole versions of the 3KF switch disconnector (Page 109)
Auxiliary switches
Size 1
Version
Auxiliary switch 1 CO
Version
Standard
Solid-state compatible
Operating current
At AC-12 / AC 230
V
A
5
-
At AC-13 / 230 V
AC
A
-
0.1
At AC-15 / AC 230
V
A
2
-
At AC-13 / 230 V
AC
A
0.2
-
Electrical connection
With soldered-on cable (finely stranded) 0.75 mm² (18 AWG), 50 cm long or with flat connectors
for conductor cross-section 0.5 – 1.5 mm² (22 – 16 AWG)
Summary of Contents for SENTRON 3KF LV HRC
Page 1: ...3KF switch disconnectors with fuses ...
Page 2: ......
Page 8: ...Table of contents 3KF switch disconnectors with fuses 6 Manual 09 2019 L1V30580914002A 01 ...
Page 110: ...Maintenance 3KF switch disconnectors with fuses 108 Manual 09 2019 L1V30580914002A 01 ...
Page 148: ...Conversion tables 3KF switch disconnectors with fuses 146 Manual 09 2019 L1V30580914002A 01 ...
Page 157: ......
Page 158: ......