3KF switch disconnectors with fuses
Manual, 09/2019, L1V30580914002A-01
115
Dimensional drawings and drilling templates
11
11.1
Distance from grounded parts and between two 3KFs
3KF LV HRC
Size
Terminal
A [mm]
B [mm]
C [mm]
D [mm]
1
Box terminals
10
0
0
10
2
Flat terminals
10
0
0
10
3
Flat terminals
10
0
0
10
4
Flat terminals
10
0
0
10
5
Flat terminals
10
0
0
10
6
Flat terminals
10
0
0
10
3KF SITOR
Size
Terminal
A [mm]
B [mm]
C [mm]
D [mm]
1
Box terminals
10
20
20
10
2
Flat terminals
10
30
30
10
3
Flat terminals
10
30
30
10
4
Flat terminals
10
30
30
10
5
Flat terminals
10
30
30
10
6
Flat terminals
10
30
30
10
Note
The dimensions A and D can be reduced to 0 mm if phase barriers or cable connection
covers are used with the 3KF.
Summary of Contents for SENTRON 3KF LV HRC
Page 1: ...3KF switch disconnectors with fuses ...
Page 2: ......
Page 8: ...Table of contents 3KF switch disconnectors with fuses 6 Manual 09 2019 L1V30580914002A 01 ...
Page 110: ...Maintenance 3KF switch disconnectors with fuses 108 Manual 09 2019 L1V30580914002A 01 ...
Page 148: ...Conversion tables 3KF switch disconnectors with fuses 146 Manual 09 2019 L1V30580914002A 01 ...
Page 157: ......