Connection and wiring
7.1 Main circuit connection
3KF switch disconnectors with fuses
48
Manual, 09/2019, L1V30580914002A-01
DC applications, 2 poles connected in series – max. 220 V DC
DC applications, 3 poles connected in series – max. 440 V DC
DC applications, 3 poles connected in series – max. 440 V DC
Summary of Contents for SENTRON 3KF LV HRC
Page 1: ...3KF switch disconnectors with fuses ...
Page 2: ......
Page 8: ...Table of contents 3KF switch disconnectors with fuses 6 Manual 09 2019 L1V30580914002A 01 ...
Page 110: ...Maintenance 3KF switch disconnectors with fuses 108 Manual 09 2019 L1V30580914002A 01 ...
Page 148: ...Conversion tables 3KF switch disconnectors with fuses 146 Manual 09 2019 L1V30580914002A 01 ...
Page 157: ......
Page 158: ......