Further accessories
8.2 Additional poles
3KF switch disconnectors with fuses
Manual, 09/2019, L1V30580914002A-01
77
4th contact element
Size 1:
On auxiliary switch modules and N and N/PE poles of size 1, two lines must be aligned on
the enclosure and the shaft. The 4th pole has to be turned clockwise as far as it will go.
Sizes 2 to 5:
The 4th pole has to be turned clockwise as far as it will go. N and N/PE poles do not have be
aligned.
Mount the additional pole on the 3KF. The additional pole must be mounted directly on the
3KF (without a gap between the switch disconnector and the additional pole).