Technical data
12.13 Undervoltage release connection data
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
181
The table below shows the values of the undervoltage releases of Family 2:
Table 12- 45 Undervoltage release family 2
MLFB
Rated voltage in V
From-to
A=0.5 mm
2
l
max
in m
A=1 mm
2
l
max
in m
A=1.5 mm
2
l
max
in m
3VL9400-1UN00
12
12
DC
0.50
1.00
1.50
3VL9400-1UP00
24
24
DC
2.00
4.00
5.99
3VL9400-1UU00
48
48
DC
7.38
14.76
22.13
3VL9400-1UV00
60
60
DC
11.46
22.92
34.37
3VL9400-1UR00
110
127
DC
48.59
97.18
145.77
3VL9400-1US00
220
250
DC
197.82
395.65
593.47
3VL9400-1UD00
24
24
AC
2.42
4.85
7.27
3VL9400-1UG00
110
127
AC
57.22
114.43
171.65
3VL9400-1UM00
208
208
AC
90.29
180.57
270.86
3VL9400-1UH00
220
250
AC
193.66
387.32
580.98
3VL9400-1UQ00
277
277
AC
228.91
457.82
686.73
3VL9400-1UJ00
380
415
AC
406.90
813.81
1220.71
3VL9400-1UK00
440
480
AC
510.87
1021.74
1532.62
Summary of Contents for SENTRON 3VL series
Page 2: ......
Page 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Page 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Page 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Page 359: ......