Description of blocks
3.2 Driver module DRV_3WL
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
52
Function Manual, 11/2008, A5E02316914A-01
I/O (parameter)
Comment
Data type
Default
Type OCM
EV_OUT6
DR 128: Event for the 6th output
BYTE
0
O
x
EV_OUT6_QC
Quality code of EV_OUT6
BYTE
0
O
EV_OUT6_OFF
DR 128: Event for the 6th output OFF
BOOL
FALSE
O
x
EV_OUT6_NA
DR 128: Event for the 6th output not
available
BOOL
FALSE
O
x
OV_LD_A
DR 129: Overload parameter IR parameter
set A (PS A)
REAL
0.0
O
x
OV_LD_A_QC
Quality code of OV_LD_A
BYTE
0
O
OV_LD_A_OFF
DR 129: Overload parameter IR parameter
set A (PS A) OFF
BOOL
FALSE
O
x
OV_LD_A_NA
DR 129: Overload parameter IR parameter
set A (PS A) not available
BOOL
FALSE
O
x
OV_LD_N_A
DR 129: Overload N-phase IN PS A (WL) REAL
0.0
O
x
OV_LD_N_A_QC
Quality code of OV_LD_N_A
BYTE
0
O
OV_LD_N_A_OFF
DR 129: Overload N-phase IN PS A (WL)
OFF
BOOL
FALSE
O
x
OV_LD_N_A_NA
DR 129: Overload N-phase IN PS A (WL)
not available
BOOL
FALSE
O
x
TL_CL_A
DR 129: Time lag class tR PS A
REAL
0.0
O
x
TL_CL_A_QC
Quality code of TL_CL_A
BYTE
0
O
TL_CL_A_OFF
DR 129: Time lag class tR PS A OFF
BOOL
FALSE
O
x
TL_CL_A_NA
DR 129: Time lag class tR PS A not
available
BOOL
FALSE
O
x
IN_PRO_PARA_A
DR 129: Instantaneous protection
parameter li PS A
REAL
0.0
O
x
IN_PRO_PARA_A_QC
Quality code of IN_PRO_PARA_A
BYTE
0
O
IN_PRO_PARA_A_OFF
DR 129: Instantaneous protection
parameter li PS A OFF
BOOL
FALSE
O
x
IN_PRO_PARA_A_NA
DR 129: Instantaneous protection
parameter li PS A not available
BOOL
FALSE
O
x
SHORT_D_PROT_A
DR 129: Short time delayed prot.
parameter lsd PS A
REAL
0.0
O
x
SHORT_D_PROT_A_QC
Quality code of SHORT_D_PROT_A
BYTE
0
O
SHORT_D_PROT_A_OFF
DR 129: Short time delayed prot.
parameter lsd PS A OFF
BOOL
FALSE
O
x
SHORT_D_PROT_A_NA
DR 129: Short time delayed prot.
parameter lsd PS A not available
BOOL
FALSE
O
x
T_STRIP_A
DR 129: Delay time for S-trip tsd PS A
REAL
0.0
O
x
T_STRIP_A_QC
Quality code of T_STRIP_A
BYTE
0
O
T_STRIP_A_OFF
DR 129: Delay time for S-trip tsd PS A
OFF
BOOL
FALSE
O
x
T_STRIP_A_NA
DR 129: Delay time for S-trip tsd PS A not
available
BOOL
FALSE
O
x
E_FLT_PROT_A
DR 129: Earth fault protection parameter
lg1 PS A
REAL
0.0
O
x
E_FLT_PROT_A_QC
Quality code of E_FLT_PROT_A
BYTE
0
O