Accessories
3.4 External accessories
Air circuit breaker 3WL10
98
Manual, 11/2017, L1V30499596002-01
Each of the locking devices listed here is available in versions for the fixed and withdrawable
breaker versions.
●
Fixed breaker:
To mount the modules on a fixed breaker, the side wall must be modified so that the main
contact position can be mechanically transmitted to the interlocking module. It is
important whether the circuit breaker is mounted on the wall or on the floor. In one case
(wall mounting), the modification must be made to the side part; in the other (floor
mounting), the base support must be modified. The necessary modification is made in the
factory before delivery for the configuration ordered by the customer. This requires the
correct article number.
Description
Version
Article number
Modification in the
factory with option
Mounting support
standard (circuit
breaker feet) for fixing
the circuit breaker on
the floor.
Fixed breaker floor
fixation
(without externally
mounted interlocking
module)
3VW9011-0BB51
A06
Mounting support
extended (circuit
breaker feet); kit incl.
mechanical transmis-
sion of switch position
on circuit breaker side
wall
Fixed breaker floor
fixation
(with externally
mounted interlocking
module)
3VW9011-0BB52
S56
Side wall extension kit,
modification for me-
chanical switch posi-
tion transmission on
circuit breaker side
wall
Fixed breaker wall
mounting
(with externally
mounted interlocking
module)
3VW9011-0BB53
S57
●
Withdrawable breaker version: Here, the modules can be directly mounted on the guide
frame; modification of the circuit breaker side wall is not required.
Mutual mechanical interlocking
With the interlocking devices, two circuit breakers can be mutually interlocked. The
interlocking device only ever releases one circuit breaker at a time, thereby ensuring that
only the released circuit breaker can be operated. The other circuit breaker remains in the
safe OFF (O) position and is blocked by the interlocking mechanism.
Both horizontally and vertically oriented circuit breakers can be mutually mechanically
interlocked.
Maximum distances between circuit breakers:
●
Horizontal: max. 2750 mm
●
Vertical: max. 1000 mm
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......