Note
On the circuit breaker, the connection from the ETU to the trip coil and its ability to function
can only be electromechanically tested after a fault, maintenance, or modification of the
device. The electronics of the instrument transformers via ETU to the trip coils are
continuously monitored during operation to ensure the greatest safety and faults are handled
immediately (tripping or only alarm).
3.5.2
TD310 Activation & Trip Box
The TD310 Activation & Trip Box is connected to the front test plug of the ETU. It can be
used with all electronic trip units of the 3- and 6-series.
Function scope:
●
Activation of the electronic trip units of the 3- and 6-series with a battery built into the test
device
●
Testing the release and the trip coil of the circuit breaker for correct functioning (trip test)
●
By activation via the TD310 Activation & Trip Box, the electronic trip units of the 6-series
can be parameterized on the display, even when the circuit breaker is switched off.
Note
Independently of an external power supply, the reasons for the last trip are always displayed
on the LEDs (ETU 3-series) or on the display (ETU 6-series) when the control key "i / Test"
is pressed. To enable this display, the ETU has a battery.
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......