Accessories
3.5 Breaker Data Adapters and test devices
Air circuit breaker 3WL10
104
Manual, 11/2017, L1V30499596002-01
3.5.3
TD410 Breaker Data Adapter
The TD410 Breaker Data Adapter is a gateway and is connected on one side with the USB
port of a PC and on the other side to the ETU of the circuit breaker via the cable supplied. It
can be used with all electronic trip units of the 3- and 6-series.
Function scope:
●
Activation of the ETU
●
Trip tests performed in the same ways as for the TD310
●
Gateway between PC and ETU
●
Parameterization of the ETUs with the powerconfig software, the standard software for
parameterization and commissioning of all communication-capable SENTRON products
(see below)
●
Documentation and archiving of the parameters set on the ETU with the powerconfig
software
See also
powerconfig (
https://support.industry.siemens.com/cs/ww/en/view/63452759
3.5.4
TD420 test device
The TD420 test device has the functionality of the TD410 with added test and storage
options. It can be used with all electronic trip units of the 3- and 6-series.
Function scope:
●
Activation of the ETU
●
Trip tests performed in the same ways as for the TD310
●
Gateway between PC and ETU
●
Parameterization of the ETU with the powerconfig software (see below)
●
Trip testing using the powerconfig software
●
Generation of a report of the parameters set on the ETU with the powerlog software
(available as of 2018).
●
Testing of the basic protection functions LSING with the powerlog software
●
Testing of the enhanced protection functions with the powerlog software
●
Test data storage with the powerlog software
●
Extended test functionality:
This is for checking the parameter settings of the ETU and comparing them with
standardized, typical applications and network circumstances. In this way, the behavior of
the circuit breaker during operation can be forecast and analyzed to prevent undesired
false tripping (supporting teach-in).
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......