Application planning
4.1 Types of installation and installation locations
Air circuit breaker 3WL10
108
Manual, 11/2017, L1V30499596002-01
The guide frame can only be used vertically upright.
Note
To integrate the circuit breaker optimally into the control cabinet, the 4-pole circuit breaker
can optionally be ordered with the neutral pole on the right or left-hand side of the circuit
breaker. These are basic versions of the circuit breaker and are permanently defined in the
circuit breaker. In all these versions, the circuit breaker is capable of full performance (no
derating, full current carrying capacity, and protection settings).
Phase sequence neutral left: N - L1 - L2 - L3
Phase sequence neutral right: L1 - L2 - L3 - N
The phase sequence L1, L2, L3 can be subsequently changed (to L3, L2, L1) by the user in
the electronic trip units of the 6-series to match any system configuration.
Mounting options
In addition to floor mounting, both the fixed breaker and the withdrawable breaker permit
direct rear wall mounting.
For floor mounting of the fixed breaker version, mounting supports are required (see Section
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......