Connection and commissioning
5.2 Mounting and connection
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
129
5.2.2
Mounting connections
The rear terminals, horizontally and vertically oriented, are configured in the factory both on
the fixed breaker version and on withdrawable breakers. All other connections are mounted
on these or different basic connections (e.g. front terminal for main circuit connection for the
fixed breaker, flange for the withdrawable breaker). The circuit breaker is delivered to the
user with the connections chosen in the basic configuration of the circuit breaker. Any
necessary installation of connections is described below.
Mounting front extended terminals for main circuit connection and circular conductor terminals 4x240
Front extended terminals for main circuit connection and circular conductor terminals are
supplied unmounted with the circuit breaker.
●
Screw the front extended terminals for main circuit connection or circular conductor
terminals to the front terminals for main circuit connection (for tightening torques, see
table Tightening torques at a glance (Page 128)).
Also note the operating instructions of the relevant connection system (see Chapter
Product-specific information (Page 7)).
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......