Connection and commissioning
5.2 Mounting and connection
Air circuit breaker 3WL10
136
Manual, 11/2017, L1V30499596002-01
Wall mounting (For the drilling template, see Chapter Switchboard panel, hole and drilling
templates, fixed breaker (Page 185)):
–
Fasten the circuit breaker to the rear wall of the switchboard panel with 4 screws with
a tightening torque of 8.6 Nm.
2.
Screw the busbars/cables of the main conductor paths to the connections of the circuit
breaker (for tightening torques, see table Tightening torques at a glance (Page 128)).
Note the operating instructions of the relevant connection system (see Chapter Product-
specific information (Page 7)).
3.
Mount the prescribed insulation accessories.
You will find information about the insulation measures in Chapter Isolating distances and
insulating equipment (Page 119). When mounting the insulation accessories, follow the
relevant Operating Instructions (see Chapter Product-specific information (Page 7)).
4.
Mount the armature plates for protection from short-circuits (see Chapter Armature plates
(Page 122)).
Note
Fixed circuit breakers do not need to be grounded.
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......