Accessories
3.2 Electronic accessories
Air circuit breaker 3WL10
78
Manual, 11/2017, L1V30499596002-01
Remote reset magnet (RR)
With the remote reset magnet (RR), the circuit breaker can be reset remotely when the
trip unit has opened the circuit breaker.
Deliberate resetting of the ETU by mechanical operation on the device or remote resetting
via the RR is necessary for safety after overcurrent tripping. All faults in the distribution board
should be cleared first.
The reset coil is available for different voltage supplies.
Technical specifications
AC
DC
Rated control
supply voltage U
s
24 V
•
•
110 V
•
•
220 V
•
•
Operating limits
90 to 110 % U
s
Spring charging motor (MO)
The spring charging motor (MO) automatically charges the closing springs when they are
discharged. If no power supply is available, the springs must be charged manually with the
hand lever of the operator on the circuit breaker.
Technical specifications
AC
DC
Rated control
supply voltage U
s
24 to 30 V
•
•
48 to 60 V
•
•
100 to 130 V
•
•
220 to 250 V
•
•
Operating limits (acc. to IEC 60947-2)
85 to 110 % U
s
Switch-on power
300 VA
300 W
Continuous power
100 VA
100 W
Make time
200 ms
Charging time
7 s
Note
The motor is always supplied with the spring charged signaling switch (S21), which signals
the state of the springs (see Section Accessories for the auxiliary and signaling switches
(Page 80)).
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......