Tightening torques at a glance
Connection technology
Tightening torque
Connection
Connection method -
Circuit breakers
[Nm]
Connection
Connection method -
Cables and busbars
1)
[Nm]
Connections of the fixed breaker version
Front terminals for main
circuit connection
18
40
Front connection bars,
extended
18
40
Horizontally orientable rear
terminals
20
18
Vertically orientable
rear terminals
20
40
Connections of the guide frame
Front terminals for main
circuit connection
12
40
Front connection bars,
extended
12
2)
40
Horizontally / vertically
orientable rear terminals
for main circuit connection
12
40
1)
You will find the dimensions for the diagrams in Chapter Power supply, grounding, and