Connection and commissioning
5.4 Commissioning
Air circuit breaker 3WL10
146
Manual, 11/2017, L1V30499596002-01
The following tests must be conducted for inspection before re-commissioning after tripping
and after lengthy storage under certain environmental conditions. These can be performed
with a TD310 test device to power the ETU. They are not mandatory for a device from the
factory because the circuit breaker is completely and thoroughly tested, including all installed
accessories, before delivery. A trip test confirms correct mechanical functioning of the
tripping plunger on the trip coil, actuated by the ETU. Electronic monitoring of the entire
connection between the current transformers, ETU, and trip coil is performed continuously by
the electronics itself (watchdog).
Items to be tested
1)
Checks
Enable alarms
Connect the ETU to a test device and check that no alarms are pre-
sent.
Status of the circuit breaker
On the ETUs of the 3-series, the status of the circuit breaker must not
be incorrect (see tables of the LED display in Chapter Alarms
(Page 161)). Perform a close/open operation on the circuit breaker
and check that no alarms have occurred.
On the ETUs of the 6-series, the status of the circuit breaker must be
correctly shown on the display. Perform a close/open operation on the
circuit breaker and check that the change in circuit breaker status is
correctly displayed.
Trip test
Make a trip attempt with the circuit breaker closed during an idle peri-
od (without circulating currents of the mains connection) and check
that the circuit breaker opens.
1)
If present
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......