Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
177
Technical specifications
8
3WL10 air circuit breaker
Breaking capacity
B
N
S
Number of poles
3, 4
Rated current
I
n
40 °C
A
630, 800, 1000, 1250
Rated operational voltage
U
e
AC (50/60 Hz)
V
Up to 690
Rated insulation voltage
U
i
AC (50/60 Hz)
V
1000
Rated impulse withstand voltage
U
imp
kV
12
Current-carrying capacity of the neutral pole for
4-pole circuit breakers
% I
n
100
Rated ultimate short-circuit breaking capacity
I
cu
415 V AC
kA
42
55
66
500 V AC
kA
42
50
50
690 V AC
kA
—
42
50
Rated service short-circuit breaking capacity
I
cs
415 V AC
kA
42
50
50
500 V AC
kA
42
50
50
690 V AC
kA
—
42
50
Rated short-circuit making capacity
I
cm
415 V AC
kA
88
121
145
500 V AC
kA
88
105
105
690 V AC
kA
—
88
105
Rated short-time withstand current
I
cw
1 s
kA
42
42
50
3 s
kA
24
24
36
Break time
I < I
cw
ms
40
I > I
cw
ms
25
Rated conditional short-circuit current of the
non-automatic air circuit breakers
I
cc
kA
—
42
50
Dimensions (3-pole)
H
mm
296
D
mm
183
W
Fixed breaker
mm
210
Withdrawable breaker mm
278
Dimensions (4-pole)
H
mm
363.5
D
mm
271
W
Fixed breaker
mm
280
Withdrawable breaker mm
348
Weight (3-pole)
Fixed breaker
kg
14
Withdrawable breaker kg
38
Weight (4-pole)
Fixed breaker
kg
16
Withdrawable breaker kg
43
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......