Accessories
3.1 Accessories for connection and insulation
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
73
3.1.2
Connections of the withdrawable breaker version
①
Horizontally / vertically orientable rear terminal for main circuit connection
②
Copper/aluminum connection bar (a cable lug is required for connection)
③
Front, extended terminal
Horizontally / vertically orientable rear terminal for main circuit connection
The rear connection with variable orientation permits connection of connecting bars and
cable lugs to the rear of the guide frame. The rear main terminal is supplied mounted on the
flange of the guide frame and can also be rotated subsequently by the user.
Copper/aluminum cable connection bar
The circular conductor terminal is mounted on the vertically oriented rear terminals of the
guide frame.
A total of up to four cables with a maximum cross section of 240 mm
2
can be connected to
the cable terminal CuAl 4 x240 mm
2
.
Extended, front connection
The extended front connection for the withdrawable breaker is an alternative to the rear
connection. It enables the connections to be accessed from the front. It is mounted directly
on the guide frame and projects beyond the guide frame contour.
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......