Accessories
3.2 Electronic accessories
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
77
Closing coil (CC) / shunt release (ST)
With the auxiliary solenoids (CC and ST), the circuit breaker can be closed and opened
remotely by electrical signals connected at the auxiliary conductor terminal system or via
communication.
Closing (breaker position CLOSED) is only possible if the closing springs are charged and
the circuit breaker is ready for closing. Opening (breaker position OPEN) is always possible.
The coils work with a current pulse ≥ 100 ms or with constant power input (100
% ON time
in %).
Note
If the opening command was issued with a shunt release, the circuit breaker can be reclosed
with a closing command after the shunt release has been switched off followed by a wait
time ≥ 30 ms.
The opening command always has priority over the closing signal.
Technical specifications
AC
DC
Rated control
supply voltage U
s
24 V
•
•
30 V
•
•
48 V
•
•
60 V
•
•
110 to 120 V
•
•
120 to 127 V
•
•
220 to 240 V
•
•
240 to 250 V
•
•
380 to 400 V
•
•
415 to 440 V
•
•
Operating limits
ST: 70 to 110 % U
s
CC: 85 to 110 % U
s
Switch-on power
300 VA
300 W
Continuous power
3.5 VA
3.5 W
Break time ST
35 ms
Make time CC
50 ms
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......