Accessories
3.4 External accessories
Air circuit breaker 3WL10
92
Manual, 11/2017, L1V30499596002-01
Summation current transformer Rc CT
Residual currents of 3 A to 30 A can be measured with a summation current transformer and
evaluated by the electronic trip unit of the 6-series, which is equipped with a rating plug for
residual current protection and the metering function MF Advanced. The transformer is
connected to the auxiliary conductor terminal system of the circuit breaker.
T7
Summation current transformer
3.4.4
Locking and interlocking
Covers and locking devices to prevent mechanical operations at the operator panel
①
Protective covers to prevent unintended mechanical operation
②
Locking device, OFF position, Ronis lock
③
Padlockable protective cover ON/OF
④
Locking device, OFF position, for padlocking