Data library
8.6 Data sets
3WL/3VL circuit breakers with communication capability - PROFIBUS
200
System Manual, 03/2011, A5E01051353-02
8.6.2
Data set DS 1 system diagnostics
The table below shows the content of data set 1 that has a length of 16 bytes and that
includes the content of DS0 in the first four bytes. Further information about diagnostics is
available in DS92.
The table below contains the data sets DS1: System diagnostics (length 16 bytes, read-
only).
Table 8- 15 Content of data set 1
Byte
Description
Data
point
Source
WL
Source VL Format Length
(bits)
Scaling
0
Identical to DS0
—
COM15
COM20
—
32
—
4
Channel type; value 0x7D
—
COM15
COM20
—
8
—
5
Length of the channel diagnostics; value 0x20
—
COM15
COM20
—
8
—
6
Number of channels; value 0x01
—
COM15
COM20
—
8
—
7
Per channel 1 bit; value 0x01
—
COM15
COM20
—
8
—
8
Reserved; value 0x00
—
COM15
COM20
—
64
—