8.7 Formats
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02
263
Table 8- 49 Format (18) "Control communication module"
Byte
Bit
Meaning
0
2
Deletes the maintenance counters
0
3
Deletes the min./max. temperatures
0
4
Deletes all min./max. values except temperature
0
5
Synchronizes the clock to xx:30:00.000
0
6
Deletes the contents of the trip log and event log
0
7
Revokes the disable on the DP address and sets the address to 126
The table below shows the format (19) "Control communication module outputs". The circuit
breaker can be switched on or off with this, for example.
Table 8- 50 Format (19) "Control communication module outputs"
Byte
Bit
Meaning
0
0
Set user output
0
1
Reset user output
0
2
Open circuit breaker
0
3
Close the circuit breaker
0
4
Switch user output mode to trip message
1
Status of user output mode
1
0
Trip is output
0
5
1
Actuated by user
0
6
Read status of user output
0
7
Read status of user input (COM15 only)
1
as of firmware version V1.13.0 of the COM15
The table below shows the format (24) "position in frame". Data point 24 specifies the
position of the SENTRON WL in the guide frame.
Table 8- 51 Format (24) "Position in frame"
Byte
Value
Meaning
0
0
Disconnected position
0
1
Connected position
0
2
Test position
0
3
Switch not available