Operation
7.4 Automatic mode - programming of the electronic module (3KC8 only)
136
Manual, 08/2017, L1V30368969104A-02
7.4.3
Step 3: Automatic configuration of the transfer switching equipment (only with
potentiometer Un = 0)
Note
You only have to carry out this step if you set the potentiometer Un to the "0" position in Step
2: Setting the potentiometer (Page 134).
The 3KC8 transfer switching equipment has an auto-configuration function for detecting and
configuring the rated values for voltage and frequency, the phase sequence, and the position
of the neutral conductor.
Requirements
●
The connections have been checked.
●
The product is ready for commissioning
●
Availability of the main source is required, optimally both sources are available
Procedure
1.
Press the "OK-Prog" button
④
for at least 2 s to measure the rated values for voltage,
frequency, the phase sequence and the position of the neutral conductor.
①
LED availability of source I
②
LED availability of source II
③
"Ready" LED
④
"OK-Prog" pushbutton
Figure 7-20 Automatic configuration
LED
①
or
②
for source availability flashes during measurement of the rated values.
The "Ready" LED
③
flashes green if the parameters have been changed but not yet
saved.
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...