Technical specifications
11.3 Technical specifications of the electronic module
Manual, 08/2017, L1V30368969104A-02
189
11.3
Technical specifications of the electronic module
Electronic module for the 3KC8 transfer switching equipment up to 3200 A
Unit
3KC8 (250 to 3200 A)
ATS settings
•
Network variants
1 + N; 3; 3 + N
•
Transfer delay
s
0 ... 60
•
Return transfer delay
min
0 ... 60
•
Frequency deviation
%
±3 … 10
•
Voltage
%
±5 … 20
Measuring inputs
Maximum rated voltage (U
n
)
•
Phase-phase
V AC
480
•
Phase-neutral
V AC
277
Metering range (L-N)
V
30 ... 332
Metering range (L-L)
V
30 ... 600
Measuring frequency
Hz
30 ... 70
Input impedance (L-L)
M
Ω
12
Number of monitored phases
1 or 3
Measuring method
True RMS
Relative error of measurement
method
%
0.5
Auxiliary supply
Connection type
Integrated dual power supply
Rated voltage (AC)
V
230
Supply voltage range (AC)
V
166 ... 332
Frequency
Hz
45 ... 65
Power loss (230 V AC)
1)
W
2.5
Impulse withstand voltage (U
imp
)
of the control circuit
kV
4
Overvoltage category of the
control circuit
III
Digital inputs
Number of inputs
Motor operator: 5
Electronic module: 6
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...