Applications
13.1 Transfer between two sources with one outgoing load
206
Manual, 08/2017, L1V30368969104A-02
Advantages of the 3KC8 series
●
Plug and play solutions
●
Compactness of the transfer switching equipment
●
Reduced number of products through all-In-one solutions
●
Installed mechanical and electrical locks
The sequence tables below apply for transfer switching equipment with electronic module
(3KC8) and 3KC4 transfer switching equipment with an appropriate, separate transfer
switching controller.
13.1
Transfer between two sources with one outgoing load
Transfer with T1 (kVA) = T2 (kVA)
The transfer switching equipment can be used for transfer between 2 sources with equal
power (T1 (kVA) = T2 (kVA) and with an outgoing load. The 3KC8 series offers the ideal
solution both for network / network applications as well as for network / generator
applications.
Figure 13-1 Transfer T1 (kVA) > T2/G (kVA)
T1
T2/G
Switching state of the
transfer switching
equipment
Load
0
0
x
OFF
1
0
P1
ON
0
1
P2
ON
1
1
P1 or P2
*
ON
* Dependent on the priority setting on the transfer switching equipment
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...