Connection
6.1 Network types
Manual, 08/2017, L1V30368969104A-02
35
6.1.2.2
Circuit diagram for the 3KC8 transfer switching equipment - 4-pole transfer switching
equipment
Figure 6-4
Three-phase 3-wire network without neutral for the 3KC8 transfer switching equipment
(4-pole)
F1
2 x 3NW6002-1
1 x 3NW7023
2 A, gG
F2
1 x 3NW6004-1
1 x 3NW7013
4 A, gG
With this arrangement there is no neutral conductor available. For this reason, the following
optional accessories can be used for establishing this network:
●
2 x autotransformer 3KC9824-1. For information, see the section titled Installing and
connecting an autotransformer (400 V / 230 V) (Page 79).
●
For the power supply: Power supply kit 3KC9830-, 3KC9831-. For information, see the
section titled Connecting power supply kit 3KC9830-, 3KC9831- (4-pole) (Page 92).
Note
The F1 fuses must be installed as closely as possible to the tap.
The F2 fuses must be fitted as closely as possible to the output of the autotransformer.
The dual power supply (DPS) accessory is not required with the 3KC8 transfer switching
equipment since it is supplied with power via two inputs of the electronic module.
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...