Connection
6.2 Connecting the main circuit
44
Manual, 08/2017, L1V30368969104A-02
Mounting bridging bars for current ratings 800 A to 1600 A
The following steps are necessary for mounting the bridging bars on the transfer switching
equipment. Refer to the table for information about the bolts, tools, and tightening torques.
The bolts for mounting the bridging bars are included in the scope of supply.
Bolts with washers and nuts are additionally required in the following quantities for fixing the
bridging bars to the connecting terminal:
●
4 x for current ratings 800 A to 1250 A
●
2 x for current rating 1600 A
Requirements
●
Power supply is switched off
●
Transfer switching equipment is in the "Manual" position
Procedure
Figure 6-13 Mounting bridging bars for current ratings 800 A to 1600 A