Connection
6.2 Connecting the main circuit
Manual, 08/2017, L1V30368969104A-02
45
Current rating
800 A ... 1000 A
M8 x 35 mm
13
8.3 ... 13
1250 A
M10 x 40 mm
17
20 ... 26
1600 A
M12 x 45 mm
19
40 ... 45
1.
Position the bridging bar on the connecting terminal.
2.
Fix the first half of the bridging bar to the connecting terminal.
–
For current ratings of 800 A to 1250 A with 4 bolts, 8 washers, and 4 nuts.
–
For current ratings of 1600 A with 2 bolts, 4 washers, and 2 nuts.
3.
Fix the second half of the bridging bar to the connecting terminal.
–
For current ratings of 800 A to 1250 A with 4 bolts, 8 washers, and 4 nuts.
–
For current ratings of 1600 A with 2 bolts, 4 washers, and 2 nuts.
Note
The two halves of the bridging bar must come into contact completely before work step 4.
4.
Connect the two parts of the bridging bar with the bolts supplied.