Connection
6.2 Connecting the main circuit
Manual, 08/2017, L1V30368969104A-02
47
Current ratings 250 A to 630 A
Requirements
●
Main circuit is disconnected
●
Transfer switching equipment is in the "Manual" position
Procedure
Figure 6-14 Connecting current ratings 250 A to 630 A
Current
rating
250 A
1 x 30 x 4 ... 1 x 32 x 5
120 ... 150
M10
20 ... 26
400 A
1 x 30 x 8 ... 1 x 32 x 8
240
M10
20 ... 26
630 A
2 x 40 x 5 ... 2 x 50 x 8
2 x 185 ... 2 x 300
M12
40 ... 45
1.
Mount the cable lug or the busbar according to the figure.
2.
Secure the connection with 1 bolt, 2 washers, and 1 nut on the cable lug or the busbar.