Connection
6.2 Connecting the main circuit
66
Manual, 08/2017, L1V30368969104A-02
Mounting and connecting sizes 7 and 8
Version 7: 2000 A to 2500 A
Version 8: 3200 A
The same components of the copper bar connection kit are required for versions 7 to 8 as for
versions 3 to 6. Mounting is also identical to mounting of versions 3 to 6. You can find more
detailed information in the section titled Connecting current ratings 250 A to 1600 A to the
main circuit (Page 46).