Connection
6.3 Connecting the control circuit
92
Manual, 08/2017, L1V30368969104A-02
6.3.5.2
Connecting power supply kit 3KC9830-, 3KC9831- (4-pole)
The power supply kit 3KC9830-, 3KC9831- for 4-pole applications with neutral conductor
enables voltage measurement and thus automatic transfer of the transfer switching
equipment (ATSE).
As well as the voltage measurement, the electronic module is supplied with power via inputs
101-102 and 201-202.
After you have installed the power supply kit between the connecting terminals in
accordance with the section titled Installing accessories for the electronic module (Page 89),
you can connect it with the electronic module. The following inputs are connected with the
cable:
●
Inputs for the power supply (101-102 and 201-202)
●
Inputs for voltage measurement (103-106 and 203-206)
1.
To connect the accessories with the electronic module, proceed as shown in the figure.
Figure 6-79 Connecting power supply kit 3KC9830-, 3KC9831-.