Connection
6.3 Connecting the control circuit
94
Manual, 08/2017, L1V30368969104A-02
A typical connection of sources I and II (3PH + N) to the electronic module of the 3KC8 is
shown in the circuit diagram below:
*
The F1 fuses are not required when using the 3KC9830-, 3KC9831- power supply kits.
Figure 6-81 Circuit diagram for a typical connection of the sources (3PH + N) to the electronic
module
If the power supply kit is not used, the following fuses are to be fitted:
F1
3 x 3NW6004-1
1 x 3NW7033
4 A, gG
Note
The F1 fuses must be installed as closely as possible to the tap.