Connection
6.1 Network types
36
Manual, 08/2017, L1V30368969104A-02
6.1.2.3
Circuit diagram for the 3KC8 transfer switching equipment - 3-pole transfer switching
equipment
Figure 6-5
Three-phase 3-wire network without neutral for the 3KC8 transfer switching equipment
(3-pole)
F1
2 x 3NW6002-1
1 x 3NW7023
2 A, gG
F2
1 x 3NW6004-1
1 x 3NW7013
4 A, gG
With this arrangement there is no neutral conductor available. For this reason, the following
optional accessories can/must be used for establishing this network:
●
2 x autotransformer 3KC9824-1. For information, see the section titled Installing and
connecting an autotransformer (400 V / 230 V) (Page 79).
●
The auxiliary conductor terminal kit is required in the case of the 3-pole variant for
connecting the electronic module, and it must be mounted before connection to the
source. See the section titled Connecting the auxiliary conductor terminal 3KC9822-,
3KC9832- for a three-phase 3-wire network (3-pole) (Page 95).
The dual power supply (DPS) accessory is not required with the 3KC8 transfer switching
equipment since it is supplied with power via two inputs of the electronic module.
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...