21
Interrupter/Operator Description
Figure 28a:
DC Control Power.
Figure 28b:
AC and DC Control Power.
Figure 28c:
AC Control Power (with Capacitor Trip).
Notes on Schematic
Arrangement
Schematics are shown with:
1. Closing Springs Discharged
2. Circuit Breaker Open
3. Circuit Breaker Located in Test,
Connect or Withdrawn
Position
Note that, in this condition, the trip latch is
free to reset, but is temporarily blocked until
the closing springs are partially recharged.
Prior to full spring charge, LS3 (NO) closes,
and LS3 (NC) opens.
Symbols
LS1
*Motor Cutoff Switch
LS2
*Spring Charged Switch
LS3
*Checks Trip Latch Reset and
Blocks Electric Close while
Racking “Test” to “Connect”
52/a
*Aux. Switch, Open when Brk. is Open
52/b
*Aux. Switch, Closed when Brk. is Open
52Y
*Anti-Pump Relay
52T
*Opening Solenoid (Trip)
52SRC *Spring Release Solenoid (Close)
88
*Spring Charging Motor
SD
*Secondary Disconnect
CS/C
*Control Switch Close
CS/T
*Control Switch Trip
R
*Red Indicating Lamp
G
*Green Indicating Lamp
W
*White Indicating Lamp
}
Typical
Remote
Devices