Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
147
DC8-001-2.09, Edition 08.2016
5.1.3 Common
Settings
•
Menu
Home | Settings
5.1.3.1 Configuration of the Target Device
The settings for the configuration of the target device reside in the directory tree under
SICAM CMIC | Master module | AU common settings
.
Here reside the basic settings for the identification of the target device (
Customer
,
Plant
,
De-
vice Name
,
Region
,
Component
).
If the target device is integrated in an existing plant, these values should fit to the existing pa-
rameterization (conformable region and component number, same customer and plant desig-
nation).
Furthermore you can enter, amongst others, the values for
Short Pulse Duration
and
Long Pulse Duration
. Depending on whether the target device receives a command with
short or with long command output time, the command is output with the duration adjusted
here.
5.1.3.1.1 Application Program
With use of an application program, the address can be set which uses the application pro-
gram for the generation of its data. The setting thereto resides under
SICAM CMIC | Master module | AU common settings | common address of ASDU
(CASDU).
CASDU1
(least significant octet) and
CASDU2
(most significant octet) result automatically in the
CASDU upon storing.
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...