Parameter
Meaning
pva_X_100%
Value adaptation: Upper limit of the used
measuring range in the external (protocol
specific) format. The corresponding internal
value is defined at Y_100%.
pva_Y_0%
Value adaptation: Lower limit of the used
measuring range in the selected internal for-
mat. The internal format is defined at TI (type
identification). The corresponding external
value is defined at X_0%.
pva_Y_100%
Value adaptation: Upper limit of the used
measuring range in the selected internal for-
mat. The internal format is defined at TI (type
identification). The corresponding external
value is defined at X_100%.
pva_Decimal_places
Count of decimal places (max. 7)
pva_Unit_text
The value is displayed with this unit text
(max. 8 characters)
Process value digital
pvd_Event
The data point is displayed in the event list
pvd_Alarm
The data point is displayed in the alarme list
pvd_Process_Text
The data point is displayed with this name
(max. 13 characters)
pvd_State_TextOn
The state ON for single or double point infor-
mation is displayed with this name (max.
6 characters)
pvd_State_TextOff
The state OFF for single or double point in-
formation is displayed with this name (max.
6 characters)
pvd_State_TextFlt
The state faulty position for double point in-
formation is displayed with this name (max.
6 characters)
pvd_State_TextInt
The state intermediate position for double
point information is displayed with this name
(max. 6 characters)
pvd_Process_GroupNbr
The data point is displayed in the cockpit in
this group (1…32)
pvd_Process_GroupPos
The data point is displayed in the cockpit on
this position (1…255)
QID-BSE
Source identification basic system element
QID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
QID-SSE
Source identification supplementary system
element
Protocol element control
message
Control_function_(PRE)
•
0...239 = function defined by protocol ele-
ment
•
240 = GI request
•
241 = reserved
•
242 = control location
•
244 = CASDU selective GI request
•
245...255 = reserve for further BSE func-
tions
Edge_(PRE)
•
Positive edge
•
Negative edge
•
State (0 = function, 1 = fu 1)
PRE_(CM)
Protocol element number
•
PRE0…PRE3
•
distribute over multimaster function
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...