Processing type
Parameter
Meaning
X_100%
Nominal range in the physical unit of the in-
put/output (100%)
-10.0 to 10.0
Y_0%
Technological or normalized value 0% (S)
-1000000000000000.000 to
1000000000000000.000
Y_100%
Technological or normalized value 100% (S)
-1000000000000000.000 to
1000000000000000.000
receive format
Source of datapoint
spontaneous
termination_t
Time between confirmation and termination (s)
0 = no termination
0 to 6553.5
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
SID-SSE
Source identification supplementary system
element