Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
217
DC8-001-2.09, Edition 08.2016
Type
Predefined Assignment
Double information to double command
(1-pole):
DI-610x with DO-6212
(2 DO-6212 with 1 DI-610x possible)
DI IOM
x
– IN D00/D01 ... command IOM
y
– OUT D00/D01
DI IOM
x
– IN D02/D03 ... command IOM
y
– OUT D02/D03
DI IOM
x
– IN D04/D05 ... command IOM
y
– OUT D04/D05
DI IOM
x
– IN D06/D07 ... command IOM
y
– OUT D06/D07
DI IOM
x
– IN D10/D11 ... command IOM
z
– OUT D00/D01
DI IOM
x
– IN D12/D13 ... command IOM
z
– OUT D02/D03
DI IOM
x
– IN D14/D15 ... command IOM
z
– OUT D04/D05
DI IOM
x
– IN D16/D17 ... command IOM
z
– OUT D06/D07
Double information to double command
(1-pole):
DI-610x with DO-6230
DI IOM
x
– IN D00/D01 … command IOM
y
– CA00/CA01
DI IOM
x
– IN D02/D03 ... command IOM
y
– CA02/CA03
DI IOM
x
– IN D04/D05 ... command IOM
y
– CA04/CA05
DI IOM
x
– IN D06/D07 ... command IOM
y
– CA06/CA07
DI IOM
x
– IN D10/D11 ... command IOM
y
– CB00/CB01
DI IOM
x
– IN D12/D13 ... command IOM
y
– CB02/CB03
DI IOM
x
– IN D14/D15 ... command IOM
y
– CB04/CB05
DI IOM
x
– IN D16/D17 ... command IOM
y
– CB06/CB07
Double information to double command
(1.5-pole):
DI-610x with DO-6212
(2 DO-6212 with 1 DI-610x possible)
DI IOM
x
– IN D00/D01 ... command IOM
y
– OUT D00/D01
DI IOM
x
– IN D02/D03 ... command IOM
y
– OUT D02/D03
DI IOM
x
– IN D04/D05 ... command IOM
y
– OUT D04/D05
DI IOM
x
– IN D10/D11 ... command IOM
z
– OUT D00/D01
DI IOM
x
– IN D12/D13 ... command IOM
z
– OUT D02/D03
DI IOM
x
– IN D14/D15 ... command IOM
z
– OUT D04/D05
Double information to double command
(1.5-pole):
DI-610x with DO-6230
DI IOM
x
– IN D00/D01 … command IOM
y
– CA00/CA01
DI IOM
x
– IN D02/D03 ... command IOM
y
– CA02/CA03
DI IOM
x
– IN D04/D05 ... command IOM
y
– CA04/CA05
DI IOM
x
– IN D06/D07 ... command IOM
y
– CA06/CA07
DI IOM
x
– IN D10/D11 ... command IOM
y
– CB00/CB01
DI IOM
x
– IN D12/D13 ... command IOM
y
– CB02/CB03
DI IOM
x
– IN D14/D15 ... command IOM
y
– CB04/CB05
DI IOM
x
– IN D16/D17 ... command IOM
y
– CB06/CB07
Double information to double command
(2-pole):
DI-610x with DO-6212
(2 DO-6212 with 1 DI-610x possible)
DI IOM
x
– IN D00/D01 ... command IOM
y
– OUT D00..D03
DI IOM
x
– IN D04/D05 ... command IOM
y
– OUT D04..D07
DI IOM
x
– IN D10/D11 ... command IOM
z
– OUT D00..D03
DI IOM
x
– IN D14/D15 ... command IOM
z
– OUT D04..D07
Double information to double command
(2-pole):
DI-610x with DO-6230
DI IOM
x
– IN D00/D01 ... command IOM
y
– CA00..CB01
DI IOM
x
– IN D02/D03 ... command IOM
y
– CA02..CB03
DI IOM
x
– IN D04/D05 ... command IOM
y
– CA04..CB05
DI IOM
x
– IN D06/D07 ... command IOM
y
– CA06..CB07
x = 0..7, y = x+1, z = x+2
Note
In each case the module DO-62xx must be equipped directly after the module DI-610x.
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...