Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
213
DC8-001-2.09, Edition 08.2016
Note
With a mixture of 1 ms and 10 ms input modules, the power monitoring should be set on an input module
with 1 ms accuracy.
You find further information in the manual
SICAM RTUs Common Functions Peripheral Ele-
ments According to IEC 60870-5-101/104, chapters "Integrated Totals via Counting Pulses",
in the section "Sensor Voltage Monitoring (Power Monitoring)"
.
Set Counter
You can set an integrated total on a defined value, if a message for set counter has been as-
signed to the respective data point (signal list).
You find the details thereto in the manual
SICAM RTUs Common Functions Peripheral Ele-
ments According to IEC 60870-5-101/104, chapter "Integrated totals via Count Pulses", sec-
tion "Set Counter" and section "Counter Interrogation"
.
Buffered Counting Pulse Acquisition
The buffered counting pulse acquisition enables the acquisition of counting pulses, even if the
target device is de-energized. Thereto a module TE-6430 must be equipped, and the DI sig-
nals to be used must be configured.
5.1.9.5.3 Current/Voltage Acquisition
For the acquisition of currents and voltages an appropriate analog input modul must be
equipped, and the AI signals to be used must be configured.
You find the functional details and the settings in the manual
SICAM RTUs Common Func-
tions Peripheral Elements According to IEC 60870-5-101/104, chapter "Currents” as well as
chapter "Voltages"
.
Note
With the modules AI-6300, AI-6307, AI-6308, AI-8320 a mixed circuitry of current and voltage is not per-
mitted .
For the direct acquisition of currents, voltages and the frequency the modules AI-8510 with
CM-8820 and AI-8511 are available.
You find the functional details and the settings in the manual
SICAM RTUs Common Func-
tions Peripheral Elements According to IEC 60870-5-101/104, chapter "Measurement in
Three-Phase Systems – I/O Module"
.
Note
If with AI-8510 the parameter transformer_X_100% is set to 100 V/
√
3, then the parameter transform-
er_Y_100% may have a value from 1 to 36 only. The parameter transformer_Y_100% may be 230 V only
if parameter transformer_X_100% is set to 230 V.
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...