Error Handling
SICAM RTUs, User Manual SICAM CMIC
327
DC8-001-2.09, Edition 08.2016
B.5
Bounce Suppression
If an input signal is bouncing, the blocked bit (
BL
) is set. The number of state changes until the
BL
bit is set, as well as the monitoring time during which the information must be static until
the
BL
bit is reset, are adjustable via constants. An output is set to
0
during the
BL
bit is set.
With an edge detection for the rising edge (
R_TRIG_INEDRISE0
) and the falling edge
(
F_EDTIMEFALL0
) the counter (
CTU_EDC0
) will be incremented by
1
. At the same time the
R
input of the counter is reset via an ON delay for the rising edge (
TON_EDTIMERISE0
) as well
as for the falling edge (
TON_EDTIMEFALL0
). With this function all state changes of the input
will be integrated by the counter (started with the first edge and triggered by each following
one).
As soon as a state change of the input happens the flag (
M_BOOL_COUNTER00
) is reset and
the input of an
AND
(module 8) is set (inverted). If the sum of state changes is greater as or
equal to a defined number (
CV
>=
PV
) the counter output is set as well, and the
BL
bit is set.
With the set
BL
bit the output is reset by another
AND
(module 9).
After termination of the monitoring time the
R
input of the counter is set again, and the counter
is reset. If the
BL
bit is set, it will be reset as well (output of module 8 is
0
).
In the procession sequence the
R
input of the counter must be reset first, because only after-
wards the positive edge at the
CU
input of the counter causes an increment. Therefore the ap-
plication program handles the
R
input before the
CU
input of the counter.
TON
TON
&
&
Parameter
1
1
CU
PV
R
Q
CTU_FLZ0
1
2
3
4
5
6
7
8
9
input
in the INIT part
R_TRIGINEDRISE0
F_TRIG_INEDFALL0
TON_EDTIMERISE0
TON_EDTIMEFALL0
M_BOOL_COUNTER00
M_BOOL_MODULE7
output
counter
upward
M_BOOL_MODULE03
blocked
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...