Cold room gate drive ATD400K
A2B00101049-01, 08/2012
41
14
Setting record
Setting record
Motor M3
(30 V / 4 A; up to 180 kg
gate weight)
Motor M4
(30V / 4 A, up to 400 kg
gate weight)
Parameter
Unit
Adjustment
range
Factory
setting
Adjustment
range
Factory
setting
Value set by
fitter
Creep distance OPEN
mm
0 … 100
30
0 ... 100
30
mm
Cutter distance OPEN
mm
0 … 100
10
0 … 100
30
mm
Creep distance CLOSE
mm
0 … 100
20
0 … 100
20
mm
Cutter distance CLOSE
mm
0 … 100
40
0 … 100
40
mm
Maximum speed OPEN
mm/s
100 … 650
650
100 … 750
600
mm/s
Creep speed OPEN
mm/s
30 … 90
40
30 … 90
40
mm/s
Cutter speed OPEN
mm/s
30 … 90
90
30 … 90
60
mm/s
Initial speed OPEN
mm/s
30 … 90
90
30 … 90
90
mm/s
Maximum speed CLOSE
mm/s
100 … 500
319
100 … 500
319
mm/s
Creep speed CLOSE
mm/s
30 … 90
60
30 … 90
60
mm/s
Cutter speed CLOSE
mm/s
30 … 90
90
30 … 90
40
mm/s
Initial speed CLOSE
mm/s
30 … 90
90
30 … 90
90
mm/s
Nudge speed CLOSE
mm/s
50 … 250
150
50 … 250
150
mm/s
Acceleration ramp OPEN
mm/s
2
300 … 1400
1300
300 … 1400 1300
mm/s
2
Braking ramp OPEN
mm/s
2
300 … 1400
600
300 … 1400 600
mm/s
2
Reversing ramp OPEN/CLOSE
mm/s
2
300 … 1400
1200
300 … 1400 1200
mm/s
2
Acceleration ramp CLOSE
mm/s
2
300 … 1400
500
300 … 1400 500
mm/s
2
Braking ramp CLOSE
mm/s
2
300 … 1400
500
300 … 1400 500
mm/s
2
Reversing ramp CLOSE/OPEN
mm/s
2
300 … 1400
850
300 … 1400 850
mm/s
2
Continuous torque (power) OPEN A
0 … 2.5
1.5
0 … 2.5
1
A
Continuous torque (power)
CLOSE
A
0 … 2.5
1.5
0 … 2.5
1
A
Cutter press-on torque
A
0 … 5
5
0 … 5
3
A
Opening force static
1
N
70 … 400
400
70 … 400
400
N
Closing force static
N
70 … 230
150
70 … 230
150
N
Cutter force static CLOSE
N
70 … 230
150
70 … 230
150
N
Nudge force static CLOSE
N
70 … 230
150
70 … 230
150
N
Special parameters
Hold-open time standard
s
0 ... 60
6
0 ... 60
6
s
Hold-open time cord-operated
switch
s
0 ... 60
0
0 ... 60
0
s
Opening width as a percentage
(%)
%
0 ... 100
100
0 ... 100
100
%
1
An opening force of 400 N is permitted for the first 10 cm of the opening movement so that the cold room gate can move
out of the CLOSED position. After 10 cm, the opening movement is limited to 300 N by the ATD400K controller.
During normal operation, parameters should always be adjusted with the gate in the CLOSED position, because the
controller then accepts the values immediately.