Controllers
4.9 Operation and configuration of the control unit
ATD4xxW Door Controller for Industrial Applications
176
System Manual, 01/2017, A5E38080677-AB
Other parameters
Table 4- 33 Other parameters
Parameter ID Adjustment range
Factory
setting
Unit
Description
Sensor Module
p4600
0
≙
inactive
1 ≙ OSSD
2 ≙ DCOPS
3 ≙ SR
0
—
Local sensor type
p4601
20 … 5000
30
ms
Discrepancy time in the function test of the OSSD
system
p4610
10 … 30000
0 ≙ "AND0" discrepancy
analysis deactivated
400
ms
Discrepancy analysis time of the input monitoring
block FBLOCK "AND0"
p4611
10 … 30000
0 ≙ discrepancy analysis
"AND2" deactivated
400
ms
Discrepancy analysis time of the input monitoring
block FBLOCK "AND2"
Faults and alarms
r2100
—
—
—
Status code
ASCII code of the 7-segment display (see section
Operating state display (Page 273))
r2102
0 ≙ special motor
1 ≙ M2
2 ≙ M3 / MDG180
3 ≙ M4 / MDG400
4 ≙ M5
255 ≙ unknown motor
Connected motor
Display and operation
p90
0 ≙ deactivated
1 ≙ activated
0
—
Write protection
Activates (1) or deactivates (0) write protection for
all travel curve parameters in the service menu.
As of V1.09: When write protection is activated via
parameter p90, the FBLOCK configuration, the
force for the learn run and the configuration of digi-
tal input 1 can no longer be changed via the operat-
ing menu.
As of V1.10: When write protection is activated, the
basic parameter cannot be changed via the operat-
ing menu.