Controllers
4.9 Operation and configuration of the control unit
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
183
Parameter ID
Adjustment range
Factory set-
ting
Unit
Description
p3867
0 ≙ deenergize
1 ≙ stop
2 ≙ open
3 ≙ close
0
—
Drive control for obstruction while reversing
p3868
0 ≙ deenergize
1 ≙ stop
2 ≙ open
3 ≙ close
0
—
Drive control after all reverses have been execut-
ed
1)
Expert parameters, see Section Expert configuration (Page 75).
The parameters in the table below refer to the opening direction only.
Table 4- 38 Obstruction and reversing parameters (in the opening direction)
Parameter ID
Adjustment range
Factory setting Unit
Description
Timing
p3869
1)
0 … 60000
1000
ms
ON-delay time for obstruction detection
p3870
1)
0 … 60000
500
ms
Minimum detection time for stop obstruction
p3871
1)
0 … 60000
100
ms
Minimum detection time for force obstruction
Ranges
p3872
1)
0 … 60000
20
mm
Distance for slow obstruction approach before
and after the obstruction
p3873
1)
0 … 60000
10
mm
Range of suppression of obstruction detection
after the closed end stop
p3874
1)
0 … 60000
10
mm
Range of suppression of obstruction detection
before the open end stop
p3875
1)
0 … 60000
20
mm
Range of suppression of force obstruction detec-
tion before the creep distance
p3876
1)
0 … 60000
50
mm
Range of suppression of force obstruction detec-
tion after the last obstruction
Retries
p3877
0 to 0xFFFF
0
≙
no retry
0xFFFF ≙ unl
imited
retries
3
0 (V1.03 and
higher)
—
Number of retries to overcome the obstruction
p3878
0 … 60000
2000
ms
Wait time before each retry
p3879
0 ≙ deenergize
1 ≙ stop
0
—
Drive control during the wait time (before retries)
p3880
0 ≙ deenergize
1 ≙ stop
2 ≙ open
3 ≙ close
0
—
Drive control after all retries have been executed
(if reversing is not configured)