ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
273
Diagnostic and maintenance
10
10.1
Operating state display
Operating states are indicated on the "H401" 7-segment display or the "H1" digital display of
the control unit.
The SIDOOR ATD410W/ATD420W/ATD430W controllers additionally enable retrieval of
status information via the parameter r2100 ("status code").
The following operating states are shown:
Display
Meaning
Info
0
1)
Light barrier / pressure-sensitive edge interrupted
6
Motor obstructed in the closing direction
c
Obstruction while opening
d
Door remains stationary during initialization run (no OPEN or CLOSE signal present, or door has reached
end position)
H
Determination of parameters (learn run)
o
Function OK
u
Door closed
Fault
1
RAM, EEPROM or CPU error (system error)
2
Braking chopper defective
3
Error in the 2nd Shutdown route
4
Motor protection, maximum opening or closing time of 65 s has been exceeded
5
Motor undefined – no learn run carried out with this motor type
(If a different motor version is used, the learn run must be repeated at power on as described in these Op-
erating Instructions. See Table 4-30 Starting a learn run when the line voltage is applied (Page 163))
7
Error in pulse generator
8
OSSD (ESPE type 2 or pressure-sensitive edge) – Function test failed
9
Motor overcurrent
E
Motor overvoltage
F
Motor undervoltage
n
Output stage defective
L
Current measurement error
t
Belt torn
U
Max. mass to be moved: